40 CFR Part 62, Table 2
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
| For these operating parameters | You must establish these operating limits | And monitor using these minimum frequencies |
|---|---|---|
| Data measurement | Data recording | Averaging time |
| Charge rate | Maximum charge rate | Continuous | Every hour | 1. Daily (batch units)2. 3-hour rolling (continuous and intermittent units) a |
| Pressure drop across the wet scrubber or amperage to wet scrubber | Minimum pressure drop or amperage | Continuous | Every 15 minutes | 3-hour rolling a |
| Scrubber liquor flow rate | Minimum flow rate | Continuous | Every 15 minutes | 3-hour rolling a |
| Scrubber liquor pH | Minimum pH | Continuous | Every 15 minutes | 3-hour rolling a |
a Calculated each hour as the average of the previous 3 operating hours.